THERE ARE THREE TYPES OF POWER GIVEN BELOW
KW - It is the power that actually power the equipment & performs useful work.
2. REACTIVE POWER/
KVAR - Non Useful Power but required to maintain and produce magnetic field/capacitor charge in magnetic equipment (relay, motor, transformer).
3. APPARENT POWER
KVA - It is the Vectorial summation of KVAR & KW.
or
Total power (Active+Reactive) drawn from the system. This determines the total load (current) on the system.
For calculate KVA , we have to determine Vectorial Summation of KVAR & KW, Look at angle between these vector.
KVA = KW + KVAR
****************
Now , Let's see What is power factor ?
POWER FACTOR
PF is the ratio of Real power to Apparent power.
PF = Real power / Apparent power
PF = KW / KVA ( where KVA = KW + KVAR)
so, PF = kw / ( kw + kvar)
or
PF = COS (angle between KW & KVA in power triangle)
or
PF = SIN (angle between KVAR & KVA in power triangle)
where , From Power Triangle
KVA² = KW ² + KVAR²
KW - It is the power that actually power the equipment & performs useful work.
2. REACTIVE POWER/
KVAR - Non Useful Power but required to maintain and produce magnetic field/capacitor charge in magnetic equipment (relay, motor, transformer).
3. APPARENT POWER
KVA - It is the Vectorial summation of KVAR & KW.
or
Total power (Active+Reactive) drawn from the system. This determines the total load (current) on the system.
For calculate KVA , we have to determine Vectorial Summation of KVAR & KW, Look at angle between these vector.
KVA = KW + KVAR
****************
Now , Let's see What is power factor ?
POWER FACTOR
PF is the ratio of Real power to Apparent power.
PF = Real power / Apparent power
PF = KW / KVA ( where KVA = KW + KVAR)
so, PF = kw / ( kw + kvar)
or
PF = COS (angle between KW & KVA in power triangle)
or
PF = SIN (angle between KVAR & KVA in power triangle)
where , From Power Triangle
KVA² = KW ² + KVAR²
0 comments:
Post a Comment